Back to catalog
300/500 V 70°C 60227 IEC 10Zoom
Low Voltage

Construction

1Conductor
Solid or circular stranded annealed copper
2Insulation
Polyvinyl chloride (PVC/C) / Phase - Blue, Brown, Black, Grey / Ground - Green/Yellow
3Inner covering
Polyvinyl chloride (PVC), Black colour
4Outer sheath
Polyvinyl chloride (PVC/ST4), Black colour
60227 IEC 10

300/500 V 70°C 60227 IEC 10

Bangkok Cable

4 CORES - LIGHT POLYVINYL CHLORIDE SHEATHED CABLE WITH GROUND

Voltage
300/500 V
Standards
TIS 11 Part 4-2553
features

Key Features

  • Flexible
  • Flame Retardant
applications

Applications

  • Suitable for general-purpose wiring.
  • For installation in raceways and shall be protected water into raceways.
  • Suitable for installation on cable trays or cable ladders.
  • Not permitted for installation in underground ducts or for direct burial in ground.
standards

Standards

  • TIS 11 Part 4-2553
specifications

Technical Data

Maximum conductor temperature
70°C
Rated voltage
300/500 V
AC test voltage
2,000 V
Markets
Industrial
specification table

Cable Size Table

13 sizes

No.of coreConductorThickness of insulationmmThickness of inner sheath coveringmm (Approx.)Thickness of outer sheathmmOverall diameterInsulation resistance at 70°CMΩ.km (Min.)Current ratingCurrent rating Laid on cable ladder at 40°C ambientACable weightkg/km (Approx.)Standard lengthm
Cross-sectional areaPhase mm² (Nominal)Cross-sectional areaGround mm² (Nominal)No. of wires(Min.)Diametermm (Approx.)Lower limitmmUpper limitmm
41.51.511.360.70.41.29.4120.01116210100/C
41.51.571.610.70.41.29.812.50.0116220100/C
42.52.511.740.80.41.211140.0122290100/C
42.52.572.030.80.41.21114.50.00922310100/C
44412.20.80.61.412.5160.008530420100/C
44472.570.80.61.413170.007730450100/C
46612.70.80.61.413.517.50.00737550100/C
46673.10.80.61.414.518.50.006537600100/C
4101013.510.61.417210.00752850500/D
4101073.9810.61.417.5220.006552920500/D
416167510.81.620.5260.0052701350500/D
4252576.331.211.624.531.50.005882050500/D
4353577.591.21.21.627350.00441102710500/D